EIM-7 type
View favorites See the comparison
This is an emergency shutoff valve device for earthquake disaster countermeasures used for the emergency shutoff system of the water tank. It does not require external power such as electric signals, and shuts off the fluid only by the operating force of the seismic sensor due to the earthquake motion.
When the seismic sensor is activated, it acts on the shutoff valve via the release mechanism, and the valve closes with the force of the spring. Restoration is a safer recovery method because the shutoff valve is opened manually after the knob of the seismic sensor is operated and the amplifier is restored.
Where to use
Water tankHigh water tankWater supply branch pipe

Major features

  • Since it is a mechanical shut-off valve, there is no need for power failure countermeasures (emergency power supply) or electrical equipment work. (Excluding switch wiring for open / close signals)
  • It can also be used in mountainous areas where there is no power supply.
  • Since the seismic sensor and shutoff valve are installed separately, the seismic sensor can be mounted on a solid stand or a sturdy wall surface that is separate from the piping system, so there is no malfunction due to piping vibration.
  • Due to its small size and light weight, it can be easily installed in existing aquariums.

specification

Product code EIM7-MA
Valve type Mechanical
type Goods
Actuation Valve closed when the seismic sensor operates (after the seismic sensor returns to the amplifier, the shutoff valve opens with the return handle (manual))
Nominal diameter 40-200 (1 1/2-8)EIM-7 type also manufactures nominal diameters of 250 and 300 (applicable pressure of 0.1 MPa or less). Please contact us for more information.
Applicable fluid waterWhen using it for a water supply device, use the EIM-7N, 7CN type, which conforms to the performance standards of the Waterworks Law.
Fluid temperature 5-60 ℃
Applicable pressure 1.0MPa or less
Protective structure Drive part rainproof typeWhen using it outdoors, please use it with a sunshade cover.
End connection Wafer type (compatible with JIS 5K and 10K flanges)
Mounting posture Upright mounting on horizontal piping
Allowable leakage amount None (visual pressure gauge)
Material body FCD (polyurethane baking finish)Please contact us as we also manufacture products other than those made by FCD.
Material Valve body SCS Please contact us if you are concerned about corrosion of the rubber sheet due to the increase in chlorine input.
Material sheet EPDM Please contact us if you are concerned about corrosion of the rubber sheet due to the increase in chlorine input.
Shutoff valve body Valve closing time About 7 seconds
Shutoff valve body accessory mechanism Limit switch (for valve closing side pump protection signal)Do not use limit switch signals when using in explosive hazards. , Includes handle for manual recovery
Seismic device operating method Weight magnet type (mechanical type)
Seismic device operation display Seismic sensor main unit display window Green: Warning display Red: Operation display
Seismic device reset method By rotating the "knob" on the front of the seismic sensor
Seismic sensor Seismic detection function Operating acceleration: 200 gal (equivalent to seismic intensity 5+)
Seismic device operation check Manual operation by rotating the "knob" on the front of the seismic sensor
Seismic device accuracy check Confirmation of operating angle by tilting the seismic sensor
Seismic device weather resistance Simple drip-proof structure-For indoor use (When using outdoors, please use the one with a special box.)Seismic sensors are also manufactured with a special box for outdoor installation (steel plate, stainless steel).
Seismic device operating temperature range -10 to 50 ° C
Seismic device Operating humidity range 90% RH or less
Seismic device release length In addition to 1,000 mm (applicable straight line distance 500 to 700 mm), according to the release length tableIf the seismic sensor is below the shutoff valve, use a release length of 1,800 mm. (Refer to page 381 of the catalog for installation.)
  • We can also manufacture an emergency shutoff system that can control two shutoff valves at the same time with one seismic sensor. (Delivery form is 1 dedicated seismic sensor and 2 shutoff valves.) Please contact us for details.

Download materials

Download materials

Common to all product symbols

EIM-7 Catalog

EIM-7 Price List

EIM-7 outline drawing

EIM-7 Instruction Manual (Japanese)

Frequently Asked Questions and Explanations

Is it possible to change the operating acceleration setting locally?

The operating acceleration cannot be changed in the field. Please contact us when ordering.

Is it possible to get a signal when a mechanical emergency shutoff valve is activated? (Answer details include a video)

The EIM-2 and 3 series are also available with an optional limit switch (no voltage). The EIM-7 series comes standard with a limit switch (no voltage) on the closed side.

Do you need a power supply?

The mechanical emergency shutoff valve does not require external power such as electrical signals, and does not require a power source because it operates only with the operating force of the seismic sensor due to seismic motion.

Inquiries about this product

Please use this form for product questions and technical inquiries.
If you would like to contact us by phone, please contact VENN's sales office.

We will strictly manage the personal information of our customers based on our "Personal Information Protection Management Regulations" and will not use it for anything other than responding to inquiries and consultations without the consent of the customer.
Please check our privacy policy.

Please cooperate with the questionnaire

We will use your opinions as a reference to make the website easier to understand and useful, so we ask for your cooperation.

Was this page helpful?

How easy was it to find the page you were looking for on this site?

How was the page easy to understand about this site?

Thank you for your cooperation

Added to Favorites View Favorites

close

Added to Download BOX Download BOX

close

Search tips

Products with different symbols depending on the product specifications are indicated by □.
When searching, please search by inputting up to the first character after the "-" (hyphen).

Notation on catalogs and websites

RD44N-F □

Contains characters that indicate pressure classification and options.

No hits in product search
RP7-FL
Hit in product search
RP7-FL
You can also search by product name or model.
product name
"Reducing valve", "solenoid valve", "safety valve", etc.
Model
"RP-6", "RD-31N", "SL-37", etc.