Pressure reducing valve (for water / liquid / door-to-door water supply), constant flow valve, water hammer preventer RD-16 type pressure reducing valve (for water / liquid)
By adopting a pressure balance structure for the valve body, the fluctuation of the secondary side pressure due to the change of the primary side pressure is small.
specification
Product code | RD16-CH | RD16-CL |
---|---|---|
Valve type | Pressure reducing valve | Pressure reducing valve |
Nominal diameter | 20-50 (3/4-2) | 20-50 (3/4-2) |
Applicable fluid | Water / liquid | Water / liquid |
Fluid temperature | 5-80 ℃ | 5-80 ℃ |
Fluid viscosity | 700cSt or less | 700cSt or less |
Primary side applied pressure | 2.7MPa or less | 2.7MPa or less |
Secondary adjustment pressure range (set pressure) | 0.3-0.7MPa See applicable pressure selection diagram | 0.05-0.35MPa See applicable pressure selection diagram |
Minimum differential pressure before and after the valve | 0.05MPa | 0.05MPa |
Deadline boost | 0.035MPa or less | 0.035MPa or less |
Allowable leakage amount | None (visual pressure gauge) | None (visual pressure gauge) |
offset | Within 0.1MPa | Within 0.07MPa |
End connection | JIS 10, 16, 20, 30K RF flangeWe also manufacture JIS 10, 16 and 20K FF flanges and ASME / JPI class 150 and 300 flanges. | JIS 10, 16, 20, 30K RF flangeWe also manufacture JIS 10, 16 and 20K FF flanges and ASME / JPI class 150 and 300 flanges. |
Mounting posture | Upright mounting on horizontal piping | Upright mounting on horizontal piping |
Material body | SCPH | SCPH |
Material Valve body | SUS | SUS |
Material Valve seat | SUS | SUS |
Material diaphragm | NBR | NBR |
Material disc | NBR | NBR |
- The material of the spring case is FC.
Download materials
Frequently Asked Questions and Explanations
What is the useful life (the number of years recommended for replacement)?
The useful life of the main unit is about 8 years, but it depends on the usage conditions and environment.
Is it possible to reduce the hydrostatic pressure (without flowing water)?
When no water is flowing (flow rate 0), the valve is closed and the secondary side holds the set pressure.
What happens if the minimum flow rate or minimum differential pressure is exceeded?
If the conditions are outside the specified range, control will be lost and operation will become unstable.
Inquiries about this product
Please use this form for product questions and technical inquiries.
If you would like to contact us by phone, please contact VENN's sales office.
We will strictly manage the personal information of our customers based on our "Personal Information Protection Management Regulations" and will not use it for anything other than responding to inquiries and consultations without the consent of the customer.
Please check our privacy policy.
Please cooperate with the questionnaire
We will use your opinions as a reference to make the website easier to understand and useful, so we ask for your cooperation.
Was this page helpful?
How easy was it to find the page you were looking for on this site?
How was the page easy to understand about this site?
Thank you for your cooperation
Added to comparison table View comparison table
Added to Favorites View Favorites
Added to Download BOX Download BOX