Pressure reducing valve (for water / liquid / door-to-door water supply), constant flow valve, water hammer preventer RD-33FNW type pressure reducing valve
It inherits controllability, reliability, and ease of use.
- Where to use
- Building equipmentFactory equipment
Major features
- Uses chlorine water resistant EPDM.
- Even if the diaphragm is damaged, water will not leak to the outside.
- It has a built-in strainer. (Nominal diameter 50 or less)
Water Supply Law Performance Standard Certification Registered Product (E-576) Pressure -Resistant Leach Durability
specification
Product code | RD33FNW-F □The symbol of the secondary adjustment pressure range is entered in □. |
---|---|
Valve type | Pressure reducing valve |
type | For 1.0MPa or less |
Nominal diameter | 65-150 (2 1/2-6) |
Applicable fluid | Water / hot water |
Fluid temperature | 5 to 90 ° C (5 to 40 ° C when using a tube end core) |
Primary side applied pressure | 1.0MPa or less |
Secondary adjustment pressure range (set pressure) | L: 0.05-0.35MPa H: Nominal diameter 100 or less: 0.3 to 0.7 MPa, Nominal diameter 125,150: 0.3 to 0.5 MPa |
Maximum decompression ratio | 10: 1 |
Minimum differential pressure before and after the valve | 0.05MPa |
Allowable leakage amount | None (visual pressure gauge) |
End connection | JIS 10K FF flange |
Mounting posture | Horizontal / vertical (excluding strainer cap upward)When installing in vertical piping, keep the nominal diameter up to 100 and allow a large maintenance space. (For nominal diameters of 125 or more, install upright on horizontal pipes.) |
strainer | Equivalent to 40 mesh (nominal diameter 50 or less) |
Material body | CAC406 |
Material diaphragm | Chlorine water resistant EPDM |
Material disc | Chlorine water resistant EPDM |
Material parts | CAC406 |
Material Spring case | Nominal diameter 15-50: ADC, Nominal diameter 65-150: FC |
- We also manufacture a pressure gauge attachment only on the secondary side. (The maximum scale of the pressure gauge is the secondary adjustment pressure range L (0.6MPa), H (1.6MPa).) * Refer to page 40 for a pressure gauge installation example.
- We also manufacture products with a built-in tube end core (nominal diameter of 50 or less).
- We also manufacture RDB-33FNW type with bypass.
Download materials
Inquiries about this product
Please use this form for product questions and technical inquiries.
If you would like to contact us by phone, please contact VENN's sales office.
We will strictly manage the personal information of our customers based on our "Personal Information Protection Management Regulations" and will not use it for anything other than responding to inquiries and consultations without the consent of the customer.
Please check our privacy policy.
Please cooperate with the questionnaire
We will use your opinions as a reference to make the website easier to understand and useful, so we ask for your cooperation.
Was this page helpful?
How easy was it to find the page you were looking for on this site?
How was the page easy to understand about this site?
Thank you for your cooperation
Added to comparison table View comparison table
Added to Favorites View Favorites
Added to Download BOX Download BOX