Safety relief valve, safety valve, relief valve SL-37V type safety relief valve
It can be shared with various fluids, vapors, gases, and liquids (metal sheet type). With its simple structure and excellent corrosion resistance, it can be widely used as a pressure vessel, safety device for various devices and devices, hot water boilers, water supply / cooling / heating equipment, and safety devices for pressure reducing valves.
- Where to use
- Pressure vesselHot water boilerHeat exchangerPressure reducing valve for secondary side
Major features
- A sealed type safety relief valve with excellent corrosion resistance for the bronze spring case, main part SCS, and spring SUS.
- It can be shared with three fluids: steam, gas, and liquid. (Metal sheet type)
- It is 1 to 2 sizes lighter and smaller than our conventional products.
Water Supply Law Performance Standard Certification Registered Product (E-442) Pressure Resistant Leach Durability
specification
Product code | SL37V-D □The pressure classification symbol is entered in □. |
---|---|
format | Lifting ceremony |
type | Soft sheet type |
Nameplate color | Blue |
Cap format | With a sealing leverIf the fluid is steam, it comes with an open lever and can be used up to 225 ° C. |
Nominal diameter | 15-50 (1/2-2) |
Applicable fluid | Air / gas / liquidPlease contact us if the fluid is gasoline, kerosene, etc., or solvent-based. |
Set pressure range | 0.05-1.0MPaPlease contact us for the set pressure range less than 0.05MPa. |
Fluid temperature | 120 ℃ or less |
End connection | JIS Rc screw |
Mounting posture | Upright mounting |
Material body | SCS |
Material Valve body | SCS (disk: FKM) |
Material Valve seat | SCS |
Material Spring case | CAC406 |
- Use the soft sheet type for frequently operated applications such as hot water boilers and heat exchangers that escape thermal expansion.
- As for the soft sheet type, we also manufacture SL-37VN and 38VN types that comply with the performance standards of the Waterworks Law.
Download materials
Frequently Asked Questions and Explanations
Please tell me the difference between the head type and the full volume type. (Answer details include a video)
There is a difference in the amount of blowout between the lift type and the total amount type. Either one can be used as long as the required amount of blowout is satisfied.
What is the purpose of the safety valve lever? (There is a video in the answer details)
This is to check if the safety valve can be operated and if there is any abnormality (sticking). (Operate when the pressure on the inlet side is 75% or more of the set pressure.)
Please tell me how to select the safety valve with lever and without lever.
As a general rule, select no lever (sealed type) for fluids that adversely affect the surroundings when the safety valve operates, such as flammable / toxic and liquid. If it is necessary to check the operation of the safety valve by operating the lever, select the one with a lever.
Inquiries about this product
Please use this form for product questions and technical inquiries.
If you would like to contact us by phone, please contact VENN's sales office.
We will strictly manage the personal information of our customers based on our "Personal Information Protection Management Regulations" and will not use it for anything other than responding to inquiries and consultations without the consent of the customer.
Please check our privacy policy.
List of related products
Please cooperate with the questionnaire
We will use your opinions as a reference to make the website easier to understand and useful, so we ask for your cooperation.
Was this page helpful?
How easy was it to find the page you were looking for on this site?
How was the page easy to understand about this site?
Thank you for your cooperation
Added to comparison table View comparison table
Added to Favorites View Favorites
Added to Download BOX Download BOX