Solenoid valve TPS-22 type temperature control solenoid valve (for steam / hot water)
Temperature control Simply connect the temperature sensor attached to the solenoid valve and the power supply, and adjust the knob to the set temperature to control the temperature.
The inter-plane dimensions are the same as the old TPS-12 and TPF-12 types.
Major features
- Since the temperature controller and solenoid valve are integrated, you are freed from troublesome selection.
- The temperature setting can be adjusted by simply turning the knob.
- It is small and does not take up space.
specification
Product code | TPS22-W |
---|---|
type | For heatingWe also manufacture for cooling (applicable fluid: water). (Product code: TPS22-WA, TPF22-WA) |
Actuation | On / off (valve open when energized) |
Nominal diameter | 10-50 (3 / 8-2) |
Applicable fluid | Steam / hot water |
Fluid temperature | 5 to 170 ° C (100 ° C or less for hot water) |
Applicable pressure | 0-0.7MPa |
Minimum differential pressure before and after the valve | 0MPa |
Allowable leakage amount | None (visual pressure gauge) |
Rated voltage | AC100V 50 / 60Hz, AC110V 60Hz or AC200V 50 / 60Hz, AC220V 60Hz |
Insulation type | H species |
Ambient temperature | 5 to 55 ° C |
Protective structure | Dustproof type for indoor use |
End connection | JIS Rc screw |
Mounting posture | Upright mounting with coil up on horizontal piping |
Material body | CAC408 |
Material Valve body | C3604 |
Material disc | PTFE |
Temperature controller input method | Resistance temperature detector: Pt500Ω (with lead wire 1.5m)The lead wire of the resistance temperature detector can be extended to 10 m with a commercially available insulated wire. (We also manufacture it.) Please contact us for other structures. |
Temperature controller control method | 2-position type |
Temperature controller set temperature range | 0-120 ℃ |
Temperature controller rated electric capacity | 2VA |
Download materials
Frequently Asked Questions and Explanations
Is there any problem if the solenoid valve is used (energized) with the valve open for a long time?
The solenoid valve coil has a "continuous rating", so there is no problem even if it is used while it is energized.
The coil of the solenoid valve is hot, is that okay? (There is a video in the answer details)
There is no problem even if the coil part is hot. Please check the video explaining the answer in detail.
If the secondary side of the solenoid valve is a rising pipe, does it flow back?
The solenoid valve is closed by the weight of the valve body and the fluid pressure. Therefore, when there is no inlet pressure and a reverse pressure is applied, the valve opens and backflow occurs. In this case, install a check valve on the secondary side of the solenoid valve.
Inquiries about this product
Please use this form for product questions and technical inquiries.
If you would like to contact us by phone, please contact VENN's sales office.
We will strictly manage the personal information of our customers based on our "Personal Information Protection Management Regulations" and will not use it for anything other than responding to inquiries and consultations without the consent of the customer.
Please check our privacy policy.
List of related products
Please cooperate with the questionnaire
We will use your opinions as a reference to make the website easier to understand and useful, so we ask for your cooperation.
Was this page helpful?
How easy was it to find the page you were looking for on this site?
How was the page easy to understand about this site?
Thank you for your cooperation
Added to comparison table View comparison table
Added to Favorites View Favorites
Added to Download BOX Download BOX